Short answer: insulation resistance is at least 100 MΩ measured at 500 V DC for one minute; dielectric withstand is 1500 V AC terminal-to-terminal and 3000 V AC terminal-to-body for one minute with a 10 mA cut-off. Both are type tests on a dry, clean sample, and both are sensitive to humidity and contamination.
What each test proves
| Test | Condition | Typical limit | What it detects |
|---|---|---|---|
| Insulation resistance | 500 V DC, 1 min | ≥ 100 MΩ | Moisture, contamination, carbon tracking |
| Dielectric withstand, pole to pole | 1500 V AC, 1 min, 10 mA cut-off | No breakdown | Creepage and clearance between circuits |
| Dielectric withstand, terminal to body | 3000 V AC, 1 min, 10 mA cut-off | No breakdown | Barrier thickness, moulding voids, flash |
| After humidity soak | Typically 48 h at 40 °C / 90 % RH | Lower limits apply | Long-term integrity of the resin |
These are the values published for our KCD1-104 rocker series: 100 MΩ minimum insulation resistance at 500 V DC, 1500 V AC between terminals and 3000 V AC between terminal and shell, one minute each with a 10 mA cut-off.
Why 500 V DC for the resistance test
A low-voltage ohm meter reads surface contamination as a moderate resistance and tells you very little. At 500 V the test finds the same weakness a mains transient would: a thin film of flux or moisture breaks down and the reading collapses from hundreds of megohms to a few megohms. That is the difference between a pass and a rejected lot.
Why the hipot voltage is higher to the body
Terminal-to-terminal clearance is set by the contact spacing inside the housing, typically 3 mm or more. Terminal-to-body clearance is just the wall of the moulding plus the air path around the terminal, and it is where a short injection shot, a void or a metal insert misalignment shows up. Hence 3000 V rather than 1500 V.
What makes a good switch fail
- Flux residue from the customer’s own PCB process, not from the switch.
- Condensation after cold storage moved into a warm room.
- Moulding flash across a barrier, invisible until the hipot trips.
- Terminal inserts pushed in too far during assembly, reducing wall thickness.
- Repeated hipot testing at the same point carbonising the surface, which then fails earlier each time.
Routine test versus type test
Full hipot on every unit is a type test in most appliance schemes; production uses a shorter, lower-stress routine test because repeated high-voltage stress degrades the insulation it is meant to prove. If your incoming inspection is hipotting every switch at 3000 V, you may be creating the failures you later find.
FAQ
What is a good insulation resistance for a switch?
100 MΩ or more at 500 V DC. Readings in the low megohms usually mean moisture or surface contamination rather than a design fault.
Can I test dielectric withstand with a multimeter?
No. It requires a hipot tester that can apply 1500–3000 V AC with a defined cut-off current.
Does passing hipot mean the switch is safe in my product?
It means the component met its own type test. Clearance to your enclosure, wiring routing and pollution degree still decide the final product.
Why does a switch fail hipot only in humid weather?
Absorbed moisture lowers surface resistivity. The part is at its limit and the season tipped it over; specify a higher tracking index material or improve the enclosure.