C14 vs C20 Inlet: Same Family, Different Current Class

dp_admin 4 min read

Short answer: C14 is a 10 A appliance inlet (15 A under UL) with a 70 °C pin temperature limit; C20 is 16 A (20 A under UL) with larger, rotated contacts. Use C14 up to about 10 A in a 70 °C envelope, and C20 above that or where the inlet runs hot.

The numbers

Item C14 inlet C20 inlet
Mates with C13 cord connector (C15 also fits) C19 cord connector (C21 also fits)
IEC rated current 10 A 16 A
North American rating up to 15 A (UL 60320-1) up to 20 A (UL 60320-1)
Max pin temperature 70 °C 70 °C
Contact orientation Horizontal pin layout Rotated layout, larger spacing
Typical use IT equipment, instruments, small PSUs Servers, UPS, rack PDU, 16 A supplies

The temperature class is the part people miss

IEC 60320 divides inlets into cold (70 °C pin), warm (120 °C) and hot (155 °C) classes. Both C14 and C20 sit in the cold class. If your enclosure runs at 80 °C near the inlet, the right move is not a C20 — it is a C16 or C16A, which are the 120 °C and 155 °C versions of the same 10 A body.

Similarly, a C20 will not solve a heat problem caused by a hot chassis: the pin limit is the same 70 °C, only the current capacity is larger.

How to choose

  1. Take the continuous current, add 20–25 % headroom, then compare with the IEC rating, not the UL one.
  2. Measure the air temperature at the inlet under full load. Above 60 °C, look at C16/C16A rather than pushing a C14.
  3. Check the cord you can actually buy. C19 cords are less common and more expensive than C13; on a low-volume product this can decide the design.
  4. Confirm the cutout and mounting holes. C14 and C20 footprints differ, and the screw pattern is not compatible.
  5. Decide on filtering and fusing in the same part: combined inlet modules exist for both sizes and save panel space.

What “10 A” really allows

A 10 A inlet is not a licence for 10 A continuous in a sealed box. Derating practice for connectors is similar to switches: keep continuous current at 80 % of rating unless the datasheet gives a temperature curve, which puts a C14 at about 8 A continuous. Above that, either the C20 or a hard-wired terminal block is the honest answer.

FAQ

Can I plug a C19 cord into a C14 inlet?

No. The contacts are larger and rotated; the connector will not enter.

Is C20 the same as C19?

No. C19 is the cord connector (female), C20 is the appliance inlet (male). They mate with each other.

Can a C14 inlet carry 16 A?

Not under IEC. UL permits 15 A on listed C13/C14 combinations, but the IEC rating remains 10 A and the pin temperature still limits continuous current.

Which inlet for a 12 A power supply?

C20. A C14 at 12 A is above its IEC rating and would run at the pin temperature limit even before enclosure heat is counted.

All twenty answers, with cutout sizes, temperature codes and contact limits side by side, are on our switch and connector answers page.